55
6. Follow the instructions in the diagram below. At each stage, allow sufficient settling time
before moving on to the next stage.
Table 15.
Manually Tuning Valve Control
Time
Process Variable
T
b
Time
Process Variable
T
a
START
Apply Power to
the load.
Does the
PV
continuously
Oscillate?
Note the time
interval T
a
Set
Pb_P
= 0.8%
Set
ArSt
= T
a
Are the
Oscillations
decaying to
zero?
Multiply
Pb_P
setting by 1.5
END
Note the period
of the decaying
oscillations (T
b
)
Multiply
Pb_P
setting by 1.5
Set
ArSt
= T
b
/2
No
Yes
Yes
No
The controller is now tuned.
Fine-tuning may be required
to optimise the controllers
response