ABOUT THIS MANUAL Modbus Programming Manual
18 Version 2
Copyright © 2012 by Despatch Industries.
All rights reserved. No part of the contents of this manual may be reproduced, copied or transmitted in any form or by any means
including graphic, electronic, or mechanical methods or photocopying, recording, or information storage and retrieval systems without
the written permission of Despatch Industries, unless for purchaser's personal use.
2.2.3. Relay Output 3 Parameters
Parameter
Name
Modbus
Address
(Dec)
Modbus
Address
(Hex)
Access
R/W
Notes
Usage
2186
0x088A
R/W
Value
Usage
0
None
1
Alarm 1
2
Alarm 2
3
Alarm 3
4
Alarm 4
5
Alarm 5
6
Event 1
7
Event 2
8
Event 3
9
Event 4
10
Event 5
11
Cycle Complete
12
Profile Running
13
Or of Alarms
14
Alarm and Events
Alarm Selection
2188
0x088C
R/W
Value
Selection
0
Alarm 1 or Alarm 2
1
Alarm 1 or Alarm 2 or Alarm 3
2
Alarm 1 or Alarm 2 or Alarm 3 or
Alarm 4
3
Alarm 1 or Alarm 2 or Alarm 3 or
Alarm 4 or Alarm 5
Event Alarm
Selection
2190
0x088E
R/W
Value
Selection
0
Alarm 1 or Event 1
1
Alarm 2 or Event 2
2
Alarm 3 or Event 3
3
Alarm 4 or Event 4
4
Alarm 5 or Event 5
2.2.4. Relay Output 4 Parameters
Parameter
Name
Modbus
Address
(Dec)
Modbus
Address
(Hex)
Access
R/W
Notes
Usage
2205
0x89D
R/W
Value
Usage
0
None
Vedere la pagina 17